The article reminds me of when Hurricane Sandy took out a bunch of New York DCs with 3+ feet of water and people were carrying diesel up stairs to keep generators running.
“The superhuman folks at the data center are hauling 55 gallon drums of diesel fuel up 17 flights of stairs. Assuming they're able to sustain a rate of transfer that exceeds the rate of consumption, the data center should run until electricity is restored. The latest estimate from Con Edison for lower Manhattan is 4 days. (The New York Stock Exchange will be open tomorrow, also running on generator power.)”
In the article he talks about living within a few minutes walk to work and telling too many people so they made him the emergency office guy. Same thing happened to me, foolishly told everyone hey I can see my apartment from here so I would get panicked calls to run in and shut down servers because the information security guy got a tip of an impending exploit about to be released on a holiday weekend with no way to do it remotely. Everyone else lived a ferry ride or commuter train away.
Not the person you asked, but I've learned that if you're not careful about what you tell your employers and/or coworkers that it will almost invariably come back to haunt you in the form of unpaid labor.
It took me an embarrassingly long time to realize that (my 30's), and now I keep my conversations with my coworkers very utilitarian and divulge minimal information about myself. I try not to be a dick or anything, I'm polite enough, but pretty much everything I talk about is either directly relevant to work and/or so surface level as to border on "vapid".
I wonder why the answer was to turn off the servers instead of turn their cooling back on. Would it not be able to stabilize the temperature fast enough?
Odd that they didn't have at minimum 1) a physical Emergency Power Off (EPO) button inside the datacenter, such that one button could de-energize everything -- usually required as part of building a datacenter due to code variance for the "low voltage" (<4000V in this context...) wiring. 2) EPO interlink to the smoke alarms, such that it would de-energize equipment automatically (maybe with delay) if smoke detected.
Realizing that I'm spoiling some of it... but we're here, so some of it is inherently spoiled...
The fire alarm klaxon went off and the siren warning
of imminent halon gas release was screaming. We
started to panic but the data center manager shouted
over the din, "Don't worry, the halon system failed
its acceptance test last week. It's disabled and
nothing will happen."
He was half right, the primary halon system indeed
failed to discharge. But the secondary halon system
observed that the primary had conked and instantly
did its duty, which was to deal with Dire Disasters.
It had twice the capacity and six times the discharge
rate.
They don't have to blow that fast. It can be regulated.
But yes, I've seen low-O2 installations also. These have other issues though, like no protection when humans need to be in there for maintenance. And the need to be very very careful when reducing it again, making sure everyone is out. It happened to my colleague once that this went wrong and while it's not low enough that you'll die, he wasn't exactly feeling great for the next few hours.
We had it at work at a datacenter right beside offices and reception.
You just have to reinforce the ceiling panels and the windows so they don't get blown out, but it's not really an issue otherwise. It was all certified and regularly checked. Water is indeed a bit counterproductive as it's not really much better than fire for the equipment in there.
PS: Halon itself is of course gone but it's other less harmful gases these days.
What also happens is low-oxygen environments (they only raise the O2 when maintenance is being done).
“The superhuman folks at the data center are hauling 55 gallon drums of diesel fuel up 17 flights of stairs. Assuming they're able to sustain a rate of transfer that exceeds the rate of consumption, the data center should run until electricity is restored. The latest estimate from Con Edison for lower Manhattan is 4 days. (The New York Stock Exchange will be open tomorrow, also running on generator power.)”
https://news.ycombinator.com/item?id=4720388 (https://web.archive.org/web/20121101194314/http://status.fog...)
https://arstechnica.com/information-technology/2012/11/how-o...
It took me an embarrassingly long time to realize that (my 30's), and now I keep my conversations with my coworkers very utilitarian and divulge minimal information about myself. I try not to be a dick or anything, I'm polite enough, but pretty much everything I talk about is either directly relevant to work and/or so surface level as to border on "vapid".
I smell AI
33 Thomas St is basically one huge datacenter, that's why it doesn't have any windows. https://en.wikipedia.org/wiki/33_Thomas_Street
[1] - https://en.wikipedia.org/wiki/Bromotrifluoromethane
So fire suppression and data centers don't mix too well
https://www.hack.org/~mc/texts/vaxen-joke.txt
Realizing that I'm spoiling some of it... but we're here, so some of it is inherently spoiled...
But yes, I've seen low-O2 installations also. These have other issues though, like no protection when humans need to be in there for maintenance. And the need to be very very careful when reducing it again, making sure everyone is out. It happened to my colleague once that this went wrong and while it's not low enough that you'll die, he wasn't exactly feeling great for the next few hours.
But it's only used in military and aviation these days anyway.
You just have to reinforce the ceiling panels and the windows so they don't get blown out, but it's not really an issue otherwise. It was all certified and regularly checked. Water is indeed a bit counterproductive as it's not really much better than fire for the equipment in there.
PS: Halon itself is of course gone but it's other less harmful gases these days.
What also happens is low-oxygen environments (they only raise the O2 when maintenance is being done).